A.O. Smith Cyclone BFC - 60 Manuel d'installation Page 76

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 98
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 75
is
Instruction manual BFC 76
F03 (lock out error)
The pressure switch
fails to work correctly
Damaged wiring/Open
circuit
1. Check the wiring between the pressure switch and the
controller
2. If necessary, replace the wiring
If the error cannot be resolved or is persistent, contact your
installation engineer
To replace the necessary parts, you must contact your installation
engineer
Pressure switch not
closing
1. Check the running speed of the fan (12.5 "Display the selected
appliance")
2. Check that the hoses on the pressure switch and the air supply
hose between fan and burner are correctly fitted. Refit them if
necessary
3. Check for cracks in the hoses on the pressure switch and in the
air supply hose between fan and burner. If necessary, replace
the hoses.
4. Check that the flue gas outlet is compliant (3.9 "Air supply and
flue").
5. Check for blockage in the flue gas discharge. Remove any
blockage that may be present
6. Check for blockage in the condensation water discharge.
Remove any blockage that may be present.
7. Measure the pressure differential across the pressure switch.
See the table in Preparation for
maintenance (15.2 "Preparation for maintenance"). If there is
insufficient pressure differential, clean the heat exchanger. If the
pressure differential is acceptable, check that the pressure
switch is closing, using a multimeter.
Code + Description Cause Solution Remark
Vue de la page 75
1 2 ... 71 72 73 74 75 76 77 78 79 80 81 ... 97 98

Commentaires sur ces manuels

Pas de commentaire